Appendix B Fieldbus Parameters
© National Instruments Corporation B-3 FieldPoint FP-3000 User Manual
Table B-1.
Error Codes
Error Code Code Description
Other 0x0001 Undefined block error condition.
Block Configuration Error 0x0002 Theblockhasdetectedanerrorinits
configuration. This usually indicates a
static parameter has been left uninitialized.
Link Configuration Error 0x0004 The logical connection between this block
and another block is misconfigured.
Simulate Active 0x0008 For I/O function blocks, this indicates that
simulation is enabled. For the resource
block, this indicates that the simulate
jumper has been set, allowing simulation
to be enabled in other blocks.
Local Override 0x0010 The block has locally overridden the
output value. This can be the result of an
interlock or faultstate.
Device Faultstate Set 0x0020 The blocks faultstate behavior is active.
Device Needs Maintenance
Soon
0x0040 The device is reporting performance
degradation that will soon require
maintenance.
Input Failure/BAD PV Status 0x0080 Either the input transducer channel has
reported a failure, or the input parameter
from an upstream block has reported a
failure. For an AI block, this could be
caused by an open circuit being detected
on the FP-AI-100 input module.
Output Failure 0x0100 The output transducer channel has reported
a failure. For an AO block, this could
indicate that the FP-AO-200 cannot drive
the current request, perhaps due to an open
circuit.
Memory Failure 0x0200 The storage for nonvolatile and static
parameters was corrupted.
Lost Static Data 0x0400 Thedevicewasunabletorestorethevalues
of static parameters after a restart.