Appendix C FP-3000 Specific Parameters
FieldPoint FP-3000 User Manual C-4 www.ni.com
DEV_OPTS
A list of device-wide options that can be turned on and off at will.
The current firmware supports only one option.
EN_CLOSE
Enables the
Close
command from parameter
OP_CMD_CXO
.If
EN_CLOSE
is not set, then
OP_CMD_CXO Close
commands will be ignored.
EN_OPEN
Enables the
Open
command from parameter
OP_CMD_CXO
.If
EN_OPEN
is
not set, then
OP_CMD_CXO Open
commands will be ignored.
EVENT_0EVENT_19
The last 20 events.
EVENT_FILTER
Restricts the entries shown in the log of the Log Block. The values are a
combination of
Configuration Error
,
Operational Warning
,and
Operational Error
.
EXECUTION_STATISTICS
A repository containing performance statistics for a given block. Use
EXECUTION_STATISTICS
to assess the performance of a given
configuration and allow appropriate changes to be made.
Table C-4. Device Options
Options Description
Disable
CFG_OPTS
in all I/O blocks This bit disables all block configuration options in
CFG_OPTS
. It is not recommended that this bit be set since
the additional behavior can make configuration easier.