Chapter 2 Installation and Configuration
© National Instruments Corporation 2-5 FieldPoint FP-3000 User Manual
3. To add more terminal bases, install them on the rail and connect their
local bus connectors together. A single FP-3000 can support up to nine
terminal bases.
4. Place the protective cover (from the bag of accessories that came with
your FP-3000) onto the local bus connector of the last terminal base on
the bank, as shown in Figure 2-3.
Figure 2-3.
Connecting Terminal Bases
Removing the FP-3000 from the DIN Rail
To remove an FP-3000 network module, unlock it from the DIN rail by
placing a screwdriver in the slot on the rail clip and opening it to the
unlocked position, as shown in Figure 2-1. Then, disconnect the FP-3000
from the local bus connector of the terminal base, and lift the FP-3000 off
the rail. You should also remove the module from the terminal base to the
right since it has a clip that snaps into the base to its left.
Caution
To avoid damaging the FP-3000 and the terminal bases, make sure that power is
not applied to the FP-3000 while you install or remove terminal bases.
Mounting the FP-3000 to a Panel
Follow these steps to install the optional FieldPoint network panel mount
accessory and mount the FP-3000 network module to a panel. You can
order the panel mount accessory, part number 777609-01, from National
Instruments.
Protective
Cover
Local Bus Connectors
Firmly Mated
Rail Clip
Locked
DIN
Rail