Chapter 3 Example Applications
FieldPoint FP-3000 User Manual 3-4 www.ni.com
3. Since the transmitter is wired to the terminals associated with channel
zero on the module, set the
FIELDPOINT_CHANNEL
parameter to
Channel 0
.
Set the Input Range
1. Click on the
FP_AI_110_RANGE
parameter on the
I/O Config
tab.
2. Set the parameter to
3.5–21 mA
, since this range most closely
matches the 420 mA that you expect from your transmitter.
Scale the Reading
1. Set the
XD_SCALE
parameter on the Scaling tab, which tells the block
the range of values to expect from the transducer. Enter the following:
XD_SCALE
EU_100 0.020
EU_0 0.004
Units_Index A
Decimal 3