Appendix F Troubleshooting
© National Instruments Corporation F-5 FieldPoint FP-3000 User Manual
Block will not leave
OOS
(Out of
Service) mode, and
BLOCK_ERR
parameter reads
Block
Configuration Error
.
Make sure you have written a non-
OOS
mode to the
TARGET
mode of the block.
Look at the
MSG
field of the parameter
LAST_BLOCK_EVENT
on the block in question. This
contains details on why the block cannot leave
OOS
mode.
If this field is blank, the block might not be scheduled to
execute; function blocks must be scheduled to change
modes. Refer to your configuration software
documentation for information about how to download a
configuration, including a schedule, to a device. If you are
using the NI-FBUS Configurator, you can also refer to
Chapter 3, Example Applications, for information on
downloading a configuration.
If this field has a message, the message tells you which
parameter of the block is misconfigured. Look up the
correct use of the parameter in the Chapter 4, Block
Reference, Appendix B, Fieldbus Parameters, or your
device documentation, and reconfigure the parameter.
Block leaves
OOS
mode but will
not go into the exact
TARGET
mode.
Your block is correctly configured, but some run-time
condition is keeping the block from reaching its target mode.
If your block is connected to other function blocks as part
of a function block application, check the status of the input
parameters. If you are using the NI-FBUS Configurator,
either look at the appropriate parameter (
IN
,
CAS_IN
,
BKCAL_IN
, etc.) in the block configuration window (with
periodic updates on) or use the Monitor functionality as
described in the NI-FBUS Configurator User Manual.If
any of these have a quality of
Bad
or
Uncertain
, examine
the blocks the inputs came from to determine the problem.
If this block is not connected to other function blocks, but
is operating standalone, check the
BLOCK_ERR
parameter
to determine the problem. If
BLOCK_ERR
reports Input
Failure or Output Failure, and this is an AI, AO, DI, DO, or
CDO block, there is likely a problem with the I/O channel.
For more information, refer to the section I/O Module
Problems.
Table F-3. Generic Software Configuration Problems (Continued)
Problem Solutions