FP-3000 Network ModuleUser ManualFieldPoint FP-3000 User ManualJuly 2000 EditionPart Number 322169B-01
ContentsFieldPoint FP-3000 User Manual x www.ni.comOUT_LO_LIM (Limiting) ...
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-22 www.ni.comSTATUS_OPTS (Faultstate, Limiting, Option)A collection of options that aff
Appendix B Fieldbus Parameters© National Instruments Corporation B-23 FieldPoint FP-3000 User ManualSTRATEGYUsed to identify groupings of blocks. Not
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-24 www.ni.comWRITE_PRI (Alarming, Option)The priority of the write alarm.XD_SCALE (Scal
© National Instruments Corporation C-1 FieldPoint FP-3000 User ManualCFP-3000 Specific ParametersFP-3000 Specific Parameters (In Alphabetical Order)A_
Appendix C FP-3000 Specific ParametersFieldPoint FP-3000 User Manual C-2 www.ni.comBLOCK_ALMS_ACTA more detailed explanation of the active block alarm
Appendix C FP-3000 Specific Parameters© National Instruments Corporation C-3 FieldPoint FP-3000 User ManualCLEAR_LOGWrite to this parameter to clear a
Appendix C FP-3000 Specific ParametersFieldPoint FP-3000 User Manual C-4 www.ni.comDEV_OPTSA list of device-wide options that can be turned on and off
Appendix C FP-3000 Specific Parameters© National Instruments Corporation C-5 FieldPoint FP-3000 User ManualEXPR_DOMAIN_INDEXVirtual field device index
Appendix C FP-3000 Specific ParametersFieldPoint FP-3000 User Manual C-6 www.ni.comFP_AO_200_RANGEAllows the range of a channel on a FieldPoint FP-AO-
Appendix C FP-3000 Specific Parameters© National Instruments Corporation C-7 FieldPoint FP-3000 User ManualFP_NOISE_REJECTIONAllows the noise rejectio
Contents© National Instruments Corporation xi FieldPoint FP-3000 User ManualWRITE_ALM (Alarming)...
Appendix C FP-3000 Specific ParametersFieldPoint FP-3000 User Manual C-8 www.ni.comHI_OUT_DDiscrete output indicating state of Hi alarm condition.INIT
Appendix C FP-3000 Specific Parameters© National Instruments Corporation C-9 FieldPoint FP-3000 User ManualLAST_RUN_ERRORThe last run error detected b
Appendix C FP-3000 Specific ParametersFieldPoint FP-3000 User Manual C-10 www.ni.comOP_CMD_CXOThe lowest level priority input. This can be used to all
Appendix C FP-3000 Specific Parameters© National Instruments Corporation C-11 FieldPoint FP-3000 User ManualVERSION_INFORMATIONThe revision of the fir
© National Instruments Corporation D-1 FieldPoint FP-3000 User ManualDAdvanced FunctionBlock BehaviorThis appendix explains advanced features of funct
Appendix D Advanced Function Block BehaviorFieldPoint FP-3000 User Manual D-2 www.ni.comFigure D-1. Parameter Connections for Cascade InitializationMo
Appendix D Advanced Function Block Behavior© National Instruments Corporation D-3 FieldPoint FP-3000 User ManualTo prevent windup, the control loop ne
Appendix D Advanced Function Block BehaviorFieldPoint FP-3000 User Manual D-4 www.ni.comcontrol. The upstream block signals to the downstream block th
© National Instruments Corporation E-1 FieldPoint FP-3000 User ManualESpecificationsThis appendix describes the specifications of the FP-3000 network
© National Instruments Corporation F-1 FieldPoint FP-3000 User ManualFTroubleshootingThe FP-3000 is a powerful and highly flexible tool you can use to
ContentsFieldPoint FP-3000 User Manual xii www.ni.comFP_RTD_TYPE ...
Appendix F TroubleshootingFieldPoint FP-3000 User Manual F-2 www.ni.comTable F-1 describes common Fieldbus communication problems andpossible solution
Appendix F Troubleshooting© National Instruments Corporation F-3 FieldPoint FP-3000 User ManualI/O Module ProblemsFP-3000 offers diagnostic capabiliti
Appendix F TroubleshootingFieldPoint FP-3000 User Manual F-4 www.ni.comSoftware Configuration ProblemsThe FP-3000 software consists of a number of fun
Appendix F Troubleshooting© National Instruments Corporation F-5 FieldPoint FP-3000 User ManualBlock will not leaveOOS(Out ofService) mode, andBLOCK_E
Appendix F TroubleshootingFieldPoint FP-3000 User Manual F-6 www.ni.comThe actual mode of a blockswitches values.A block, such as a PID, may switch mo
Appendix F Troubleshooting© National Instruments Corporation F-7 FieldPoint FP-3000 User ManualCommon QuestionsWhat can I do that would cause big prob
Appendix F TroubleshootingFieldPoint FP-3000 User Manual F-8 www.ni.comoperator in Lookout to theTRK_IN_D.VALUEof the PID object.Connect the Pot for t
Appendix F Troubleshooting© National Instruments Corporation F-9 FieldPoint FP-3000 User ManualHow Many PID Loop Iterations per Second Can the FP-3000
Appendix F TroubleshootingFieldPoint FP-3000 User Manual F-10 www.ni.comNote that if you want to monitor values with an HMI package on the hostmachine
Appendix F Troubleshooting© National Instruments Corporation F-11 FieldPoint FP-3000 User ManualFollow these steps to use the NI-FBUS Dialog utility t
Contents© National Instruments Corporation xiii FieldPoint FP-3000 User ManualSoftware Configuration Problems ...
Appendix F TroubleshootingFieldPoint FP-3000 User Manual F-12 www.ni.com13. Under the appropriate manufacturer directory, there is a directory foreach
© National Instruments Corporation G-1 FieldPoint FP-3000 User ManualGTechnical Support ResourcesWeb SupportNational Instruments Web support is your f
Appendix G Technical Support ResourcesFieldPoint FP-3000 User Manual G-2 www.ni.comWorldwide SupportNational Instruments has offices located around th
© National Instruments Corporation Glossary-1 FieldPoint FP-3000 User ManualGlossaryPrefix Meanings Valuem- milli- 10–3M- mega- 106Numbers4-20 mA syst
GlossaryFieldPoint FP-3000 User Manual Glossary-2 www.ni.comBBandwidth The range of frequencies present in a signal, or the range offrequencies to whi
Glossary© National Instruments Corporation Glossary-3 FieldPoint FP-3000 User ManualContained parameter A parameter that does not receive or send data
GlossaryFieldPoint FP-3000 User Manual Glossary-4 www.ni.comEEvent An occurrence on a device that causes a Fieldbus entity to send theFieldbus event m
Glossary© National Instruments Corporation Glossary-5 FieldPoint FP-3000 User ManualGGround An intentional or accidental conducting path between an el
GlossaryFieldPoint FP-3000 User Manual Glossary-6 www.ni.comLink AFOUNDATIONFieldbus network is made up of devices connected bya serial bus. This seri
Glossary© National Instruments Corporation Glossary-7 FieldPoint FP-3000 User ManualNI-FBUS CommunicationsManagerSoftware shipped with National Instru
© National Instruments Corporation 1-1 FieldPoint FP-3000 User Manual1FP-3000 Network ModuleOverviewRelated DocumentationThe following documents conta
GlossaryFieldPoint FP-3000 User Manual Glossary-8 www.ni.comProcess variable A common Fieldbus function block parameter representing somevalue in the
Glossary© National Instruments Corporation Glossary-9 FieldPoint FP-3000 User ManualSignal An extension of the IEEE 488.2 standard that defines a stan
GlossaryFieldPoint FP-3000 User Manual Glossary-10 www.ni.comVV Vo l t sVDC Volts Direct Current.VFDSee Virtual Field Device.Virtual Field Device The
© National Instruments Corporation Index-1 FieldPoint FP-3000 User ManualIndexNumbers4-20 mA pressure sensor, converting to Fieldbus(example), 3-2 to
IndexFieldPoint FP-3000 User Manual Index-2 © National Instruments CorporationBKCAL_HYS parameter, B-2BKCAL_IN parameter, B-2BKCAL_OUT parameter, B-2B
Index© National Instruments Corporation Index-3 FieldPoint FP-3000 User Manualsoftware configurationproblems, F-4 to F-7generic software configuration
IndexFieldPoint FP-3000 User Manual Index-4 © National Instruments Corporationbringing block online, 3-6creating FP-AI-110 block, 3-3getting started,
Index© National Instruments Corporation Index-5 FieldPoint FP-3000 User ManualDD_REV, B-6DEV_REV, B-6DEV_TYPE, B-6DISC_ALM, B-6DISC_LIM, B-6DISC_PRI,
IndexFieldPoint FP-3000 User Manual Index-6 © National Instruments CorporationSHED_RCAS, B-20SHED_ROUT, B-20SIMULATE, B-20SIMULATE_D, B-21SP, B-21SP_D
Index© National Instruments Corporation Index-7 FieldPoint FP-3000 User ManualLAST_BLOCK_EVENT(table),C-8toC-9LAST_RUN_ERROR, C-9LO_LO_OUT_D, C-9LO_OU
Chapter 1 FP-3000 Network Module OverviewFieldPoint FP-3000 User Manual 1-2 www.ni.comeach 4–20 mA device to your controller, you can mount an FP-3000
IndexFieldPoint FP-3000 User Manual Index-8 © National Instruments CorporationGGAIN parameter, B-9get_status function (table), 4-13GRANT_DENY paramete
Index© National Instruments Corporation Index-9 FieldPoint FP-3000 User ManualI/O modulesmounting onto terminal bases, 2-7 to 2-9inserting new I/O mod
IndexFieldPoint FP-3000 User Manual Index-10 © National Instruments Corporationmodule and channel selectionconverting 4-20 mA pressure sensor toFieldb
Index© National Instruments Corporation Index-11 FieldPoint FP-3000 User Manualbringing block online, 3-6creating FP-AI-110 block, 3-3scalingthereadin
IndexFieldPoint FP-3000 User Manual Index-12 © National Instruments Corporationsoftware configuration problems, F-4 to F-7generic software configurati
Index© National Instruments Corporation Index-13 FieldPoint FP-3000 User Manualterminal basesavoiding damage while adding orremoving (note), 1-5connec
Chapter 1 FP-3000 Network Module Overview© National Instruments Corporation 1-3 FieldPoint FP-3000 User Manualto form a distributed control system. Fu
Chapter 1 FP-3000 Network Module OverviewFieldPoint FP-3000 User Manual 1-4 www.ni.comInteroperabilityThe FP-3000 network module can send or receive d
Chapter 1 FP-3000 Network Module Overview© National Instruments Corporation 1-5 FieldPoint FP-3000 User ManualCautionTo avoid damaging the network mod
© National Instruments Corporation 2-1 FieldPoint FP-3000 User Manual2Installation and ConfigurationImport Device DescriptionsThe device description f
SupportWorldwide Technical Support and Product Informationwww.ni.comNational Instruments Corporate Headquarters11500 North Mopac Expressway Austin, Te
Chapter 2 Installation and ConfigurationFieldPoint FP-3000 User Manual 2-2 www.ni.comThe next layer of folders is the device type. For example, the FP
Chapter 2 Installation and Configuration© National Instruments Corporation 2-3 FieldPoint FP-3000 User ManualMount the FP-3000 and Terminal BasesYou c
Chapter 2 Installation and ConfigurationFieldPoint FP-3000 User Manual 2-4 www.ni.comFigure 2-2. Mounting the FP-3000 onto a DIN Rail3. Slide the FP-3
Chapter 2 Installation and Configuration© National Instruments Corporation 2-5 FieldPoint FP-3000 User Manual3. To add more terminal bases, install th
Chapter 2 Installation and ConfigurationFieldPoint FP-3000 User Manual 2-6 www.ni.com1. Use a flat-bladed screwdriver to open the rail clip to the unl
Chapter 2 Installation and Configuration© National Instruments Corporation 2-7 FieldPoint FP-3000 User Manual3. Bolt, screw, or otherwise fasten the t
Chapter 2 Installation and ConfigurationFieldPoint FP-3000 User Manual 2-8 www.ni.comFigure 2-5. Mounting I/O Module to Terminal BaseRemoving I/O Modu
Chapter 2 Installation and Configuration© National Instruments Corporation 2-9 FieldPoint FP-3000 User ManualHot-swap a module only with a compatible
Chapter 2 Installation and ConfigurationFieldPoint FP-3000 User Manual 2-10 www.ni.comFigure 2-7. FP-3000 Connector PinoutConnect Power to the FP-3000
Chapter 2 Installation and Configuration© National Instruments Corporation 2-11 FieldPoint FP-3000 User ManualThe Vsupply and Common of input modules
Important InformationWarrantyThe FieldPoint FP-3000 network module is warranted against defects in materials and workmanship for a period of one year
Chapter 2 Installation and ConfigurationFieldPoint FP-3000 User Manual 2-12 www.ni.comCalculating Power for a FieldPoint BankThe power requirements fo
Chapter 2 Installation and Configuration© National Instruments Corporation 2-13 FieldPoint FP-3000 User ManualFigure 2-8.FP-3000 Power Connector Pinou
Chapter 2 Installation and ConfigurationFieldPoint FP-3000 User Manual 2-14 www.ni.comIf the self-test suite fails, the FP-3000 does not participate i
Chapter 2 Installation and Configuration© National Instruments Corporation 2-15 FieldPoint FP-3000 User ManualThe multicolored PROCESS LED is used to
Chapter 2 Installation and ConfigurationFieldPoint FP-3000 User Manual 2-16 www.ni.comAutoconfigure the FP-3000The autoconfiguration capabilities of t
Chapter 2 Installation and Configuration© National Instruments Corporation 2-17 FieldPoint FP-3000 User Manual7. Click on Run and change it toAutoconf
© National Instruments Corporation 3-1 FieldPoint FP-3000 User Manual3Example ApplicationsThis chapter provides examples that show you how to configur
Chapter 3 Example ApplicationsFieldPoint FP-3000 User Manual 3-2 www.ni.comIf you need more help setting up your network, refer to the NI-FBUSConfigur
Chapter 3 Example Applications© National Instruments Corporation 3-3 FieldPoint FP-3000 User ManualCreate an FP-AI-110 BlockYou must create a block fo
Chapter 3 Example ApplicationsFieldPoint FP-3000 User Manual 3-4 www.ni.com3. Since the transmitter is wired to the terminals associated with channelz
ConventionsThe following conventions are used in this manual:» The » symbol leads you through nested menu items and dialog box optionsto a final actio
Chapter 3 Example Applications© National Instruments Corporation 3-5 FieldPoint FP-3000 User ManualThis tells the AI block to expect readings in the r
Chapter 3 Example ApplicationsFieldPoint FP-3000 User Manual 3-6 www.ni.com3. To download this schedule to the device, select Configure»DownloadConfig
Chapter 3 Example Applications© National Instruments Corporation 3-7 FieldPoint FP-3000 User ManualExample 2: Temperature Control with the FP-3000One
Chapter 3 Example ApplicationsFieldPoint FP-3000 User Manual 3-8 www.ni.comTaking Temperature ReadingsTipIf you autoconfigured your FP-3000, you can s
Chapter 3 Example Applications© National Instruments Corporation 3-9 FieldPoint FP-3000 User ManualSet the Input Range and Thermocouple Type1. Clickon
Chapter 3 Example ApplicationsFieldPoint FP-3000 User Manual 3-10 www.ni.com3. Set the block to use linear scaling by setting theL_TYPEparameter onthe
Chapter 3 Example Applications© National Instruments Corporation 3-11 FieldPoint FP-3000 User ManualControlling a Heating ElementTipIf you autoconfigu
Chapter 3 Example ApplicationsFieldPoint FP-3000 User Manual 3-12 www.ni.comScale the Output1. You can avoid setting theXD_SCALEvalue manually if you
Chapter 3 Example Applications© National Instruments Corporation 3-13 FieldPoint FP-3000 User ManualOnce the block goes toAuto, it is fully operationa
Chapter 3 Example ApplicationsFieldPoint FP-3000 User Manual 3-14 www.ni.comScale the PIDDouble-click on the PID block you created to launch the block
© National Instruments Corporation v FieldPoint FP-3000 User ManualContentsChapter 1FP-3000 Network Module OverviewRelated Documentation...
Chapter 3 Example Applications© National Instruments Corporation 3-15 FieldPoint FP-3000 User ManualAt this point, you could either use a template or
Chapter 3 Example ApplicationsFieldPoint FP-3000 User Manual 3-16 www.ni.comDownload and Bring the Loop into Auto1. To download this schedule to the d
Chapter 3 Example Applications© National Instruments Corporation 3-17 FieldPoint FP-3000 User ManualTypical values forGAIN,RESET,andRATEare:Set Alarms
© National Instruments Corporation 4-1 FieldPoint FP-3000 User Manual4Block ReferenceThis chapter describes the function blocks and the parameters sup
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-2 www.ni.comcommunication between function blocks on different devices are scheduleddetermin
Chapter 4 Block Reference© National Instruments Corporation 4-3 FieldPoint FP-3000 User ManualResource BlockThe resource block, defined by the FOUNDAT
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-4 www.ni.comDO (Discrete Output)The DO block writes to a discrete output channel. This block
Chapter 4 Block Reference© National Instruments Corporation 4-5 FieldPoint FP-3000 User ManualExpression Block (FP-3000 Specific)The Expression block
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-6 www.ni.comStatus Calculation RulesTo simplify status calculation for simple cases, the Exp
Chapter 4 Block Reference© National Instruments Corporation 4-7 FieldPoint FP-3000 User Manual• C-language style program constructs—Program statements
ContentsFieldPoint FP-3000 User Manual vi www.ni.comLED Indicators ...
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-8 www.ni.comNoteUse the spreadsheetfp3kexpr.xlsprovided with the FP-3000 package to generate
Chapter 4 Block Reference© National Instruments Corporation 4-9 FieldPoint FP-3000 User ManualOperatorsOperators let you manipulate the Expression blo
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-10 www.ni.comFlow ControlFlow control and grouping constructs supported by the expressionlan
Chapter 4 Block Reference© National Instruments Corporation 4-11 FieldPoint FP-3000 User ManualFunction DescriptionsTable 4-5. Function OperatorsClass
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-12 www.ni.comFunction Nameis_goodFunction SyntaxUint32 is_good(vs_float F) OR Uint32 is_good
Chapter 4 Block Reference© National Instruments Corporation 4-13 FieldPoint FP-3000 User ManualFunction Nameset_statusFunction Syntaxvs_discrete set_s
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-14 www.ni.comUser FunctionsUser functions are not supported. You cannot define sub-routines
Chapter 4 Block Reference© National Instruments Corporation 4-15 FieldPoint FP-3000 User ManualSupported FieldPoint Modules and ChannelsThe FP-3000 su
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-16 www.ni.comPID ControlIn a Fieldbus network, a PID control loop is composed of three funct
Chapter 4 Block Reference© National Instruments Corporation 4-17 FieldPoint FP-3000 User ManualPID Loop Execution TimeThe FP-3000 can run approximatel
Contents© National Instruments Corporation vii FieldPoint FP-3000 User ManualChapter 4Block ReferenceBlock Overview ...
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-18 www.ni.commilliseconds). The NI-FBUS Configurator does not allow function blocksto be sch
Chapter 4 Block Reference© National Instruments Corporation 4-19 FieldPoint FP-3000 User ManualAlarm ParametersEach block contains a fixed set of alar
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-20 www.ni.comdiscussed above). The confirmation message confirms that the message hasmade it
Chapter 4 Block Reference© National Instruments Corporation 4-21 FieldPoint FP-3000 User ManualStatus refers to the quality of a variable communicated
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-22 www.ni.comSubstatusTheSubstatusfield is used to describe more specifically the cause of t
Chapter 4 Block Reference© National Instruments Corporation 4-23 FieldPoint FP-3000 User ManualACTUAL ModeAn indicator of the current mode of executio
Chapter 4 Block ReferenceFieldPoint FP-3000 User Manual 4-24 www.ni.comCascadeCas(0x04)The block operates normally with a setpointspecified automatica
© National Instruments Corporation A-1 FieldPoint FP-3000 User ManualAConfiguring the FP-3000The FP-3000 has three configuration switches accessible f
Appendix A Configuring the FP-3000FieldPoint FP-3000 User Manual A-2 www.ni.comWrite LockWhen On, the device rejects writes to block configuration par
© National Instruments Corporation B-1 FieldPoint FP-3000 User ManualBFieldbus ParametersFieldbus Parameters (In Alphabetical Order)ACK_OPTION (Alarmi
ContentsFieldPoint FP-3000 User Manual viii www.ni.comAppendix AConfiguring the FP-3000Simulate Enable...
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-2 www.ni.comBIAS (Tuning)The bias value, in engineering units, used to calculate the fu
Appendix B Fieldbus Parameters© National Instruments Corporation B-3 FieldPoint FP-3000 User ManualTable B-1.Error CodesError Code Code DescriptionOth
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-4 www.ni.comBYPASS (Scaling, Tuning)Allows the normal control algorithm to be bypassed
Appendix B Fieldbus Parameters© National Instruments Corporation B-5 FieldPoint FP-3000 User ManualCLR_FSTATE (Faultstate, Option)Writing Clear to thi
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-6 www.ni.comCYCLE_SEL (Tuning)Identifies the block execution methods available. Unused
Appendix B Fieldbus Parameters© National Instruments Corporation B-7 FieldPoint FP-3000 User ManualDISC_PRI (Alarming)Priority of the discrete alarm.D
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-8 www.ni.comFF_GAIN (Scaling, Tuning)The gain by which the feed-forward input is multip
Appendix B Fieldbus Parameters© National Instruments Corporation B-9 FieldPoint FP-3000 User ManualFIELD_VAL_D (Process, Scaling, Tuning)The value fro
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-10 www.ni.comNoteThe device does not use this parameter to restrict parameter access it
Appendix B Fieldbus Parameters© National Instruments Corporation B-11 FieldPoint FP-3000 User ManualHI_PRI (Alarming)The priority of the high limit al
Contents© National Instruments Corporation ix FieldPoint FP-3000 User ManualDV_LO_PRI (Alarming)...
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-12 www.ni.comITK_VERThe version of the Interoperability Test Kit with which this device
Appendix B Fieldbus Parameters© National Instruments Corporation B-13 FieldPoint FP-3000 User ManualLIM_NOTIFY (Alarming)A limit on the number of unco
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-14 www.ni.comMAX_NOTIFY (Alarming)The maximum number of unconfirmed alarm/event notific
Appendix B Fieldbus Parameters© National Instruments Corporation B-15 FieldPoint FP-3000 User ManualNV_CYCLE_T (Diagnostic)The regular time interval,
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-16 www.ni.comOUT (Process, Scaling, Tuning)The current output value of the block.OUT_D
Appendix B Fieldbus Parameters© National Instruments Corporation B-17 FieldPoint FP-3000 User ManualPV_D (Process)The process variable, or primary var
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-18 www.ni.comRCAS_IN_D (Mode Shedding, Process)The discrete cascade input for a control
Appendix B Fieldbus Parameters© National Instruments Corporation B-19 FieldPoint FP-3000 User ManualCautionUsingRestart to Defaultscauses all your con
Appendix B Fieldbus ParametersFieldPoint FP-3000 User Manual B-20 www.ni.comSET_FSTATE (Faultstate, Option)Allows the user to set the device faultstat
Appendix B Fieldbus Parameters© National Instruments Corporation B-21 FieldPoint FP-3000 User ManualSIMULATE_D (Option)Used to bypass the physical I/O