FIELDPOINT
OPERATING INSTRUCTIONS
AND SPECIFICATIONS
FP-DO-403 and cFP-DO-403
16-Channel, 5 to 30 V Sinking Digital Output Module
These operating instructions describe how to install and use the
National Instruments FP-DO-403 and cFP-DO-403 digital output
modules, referred to inclusively as the [c]FP-DO-403. For
information about configuring and accessing the [c]FP-DO-403
over a network, refer to the user manual for the FieldPoint network
module you are using.
Features
The [c]FP-DO-403 is a FieldPoint digital output module with the
following features:
16 sinking digital output channels
Outputs that sink 2 A per channel, 16 A
2
per module
Compatible with voltages from 5 to 30 VDC
250 V
rms
CAT II continuous channel-to-ground isolation,
verified by 2,300 V
rms
, 5 s dielectric withstand test
40 to 70 °C operation
ON/OFF LED indicators
Hot swappable
Installing the FP-DO-403
The FP-DO-403 mounts on a FieldPoint terminal base (FP-TB-x),
which provides operating power to the module. Installing the
FP-DO-403 onto a powered terminal base does not disrupt the
operation of the bank.
To install the FP-DO-403, refer to Figure 1 and complete the
following steps:
1. Slide the terminal base key to either position X, used for any
module, or position 6, used for the FP-DO-403 module.
Vista de pagina 0
1 2 3 4 5 6 ... 14 15

Indice de contenidos

Pagina 1 - FP-DO-403 and cFP-DO-403

FIELDPOINT™ OPERATING INSTRUCTIONSAND SPECIFICATIONSFP-DO-403 and cFP-DO-40316-Channel, 5 to 30 V Sinking Digital Output ModuleThese operating instruc

Pagina 2 - Installing the cFP-DO-403

[c]FP-DO-403 10 ni.comCaution For Zone 2 applications, install a protection device across the external power supply and the COM terminal. The device m

Pagina 3 - Wiring the [c]FP-DO-403

© National Instruments Corp. 11 [c]FP-DO-403Power RequirementsPower from network module ... 600 mWSafety Isolation VoltageIsolation voltage i

Pagina 4 - [c]FP-DO-403 4 ni.com

[c]FP-DO-403 12 ni.comSafetyThis product is designed to meet the requirements of the following standards of safety for electrical equipment for measur

Pagina 5

© National Instruments Corp. 13 [c]FP-DO-403contains the environmental regulations and directives with which NI complies, as well as other environment

Pagina 6 - Digital Output Circuit

[c]FP-DO-403 14 ni.comWhere to Go for SupportFor more information about setting up the FieldPoint system, refer to these National Instruments document

Pagina 7 - Status Indicators

© 2002–2007 National Instruments Corp. All rights reserved.373354C-01 Aug07National Instruments, NI, ni.com, and LabVIEW are trademarks of National In

Pagina 8 - [c]FP-DO-403 8 ni.com

[c]FP-DO-403 2 ni.com2. Align the FP-DO-403 alignment slots with the guide rails on the terminal base.3. Press firmly to seat the FP-DO-403 on the ter

Pagina 9

© National Instruments Corp. 3 [c]FP-DO-403Figure 2. Installing the cFP-DO-403Wiring the [c]FP-DO-403The FP-TB-x terminal base has connections for ea

Pagina 10 - Specifications

[c]FP-DO-403 4 ni.comloads on the output channels, up to 2 A per channel.1 Connect the external power supply to multiple V and VSUP terminals and to m

Pagina 11 - Shock and Vibration

© National Instruments Corp. 5 [c]FP-DO-403Figure 3. Wiring for Low-Current ApplicationsWiring for High-Current ApplicationsIf your application requi

Pagina 12 - Environmental Management

[c]FP-DO-403 6 ni.comDigital Output CircuitThe [c]FP-DO-403 digital output channels are optically isolated from the rest of the FieldPoint bank. In th

Pagina 13 - Mechanical Dimensions

© National Instruments Corp. 7 [c]FP-DO-403mount the flyback diode within 18 in. of the load. Figure 5 shows a flyback diode connected to an inductive

Pagina 14 - Where to Go for Support

[c]FP-DO-403 8 ni.com250 Vrms Measurement Category II continuous isolation, verified by 2,300 Vrms, 5 s dielectric withstand test. The [c]FP-DO-403 pr

Pagina 15 - 373354C-01 Aug07

© National Instruments Corp. 9 [c]FP-DO-403•Do not use the [c]FP-DO-403 as the only isolating barrier between human contact and working voltages highe