National Instruments Corporation E-1 FieldPoint FP-3000 User Manual
E
Specifications
This appendix describes the specifications of the FP-3000 network module.
All FieldPoint network modules undergo extensive testing for operating
under rugged environmental conditions that exist in industrial applications.
FieldPoint network modules are designed and tested for immunity and
susceptibility, as well as for emissions.
Network
FP-3000.................................................. FOUNDATION Fieldbus H1
Integrity.................................................. Checksum
Power Supply Range.............................. 11 to 30 VDC
Power Consumption............................... 6 watt + 1.15 * (I/O Module
Consumption)
Maximum Terminal Bases per Bank .....9
Maximum Number of Banks per
Fieldbus segment (without repeaters) .... 32
Environment
Operating Temperature .......................... –40° to +60° C
Storage Temperature.............................. –55° to +100° C
Relative Humidity.................................. 5% to 90% noncondensing
Compliance
Electrical Safety ..................................... designed to meet IEC 1010
EMI Emissions/Immunity...................... CISPR 11