FieldPoint
TM
cFP-20
xx
Quick Start Guide
What You Need
to Get Set Up
• cFP-20
xx
LabVIEW RT controller
Mounting hardware (DIN rail, panel-
mount, or rack-mount accessory)
I/O module(s)
Connectivity accessories: connector
blocks, cables
11–30 V power supply
Accessories: Ethernet cable,
screwdriver
PC running Windows
FieldPoint software 3.0.2 or later
LabVIEW RT
106 mm [4.18 in.]
Cabling
Clearance
Min. 182 mm [7.18 in.]
4 slots = 246 mm (9.68 in.)
8 slots = 441 mm (17.4 in.)
Cooling Outline
50.8 mm [2.00 in.]
Cooling Outline
50.8 mm [2.00 in.]
MMoouunntt tthhee CCoommppaacctt FFiieellddPPooiinntt BBaacckkppllaannee
You can mount the cFP-BP-
x
backplane on a 35 mm DIN rail, on a panel, or in a standard 19 in. rack.
Before using any of these mounting methods, record the serial number from the back of the backplane.
1
127 mm [5.00 in.]
Cabling
Clearance
Min. 165 mm [6.50 in.]
Cooling Outline
51–76 mm [2–3 in.]
All Around
4 slots = 246 mm (9.68 in.)
8 slots = 441 mm (17.4 in.)
CCAAUUTTIIOONN
Keep in mind these requirements for space and cabling clearance:
Allow at least 51 mm (2 in.) all around the backplane for air circulation.
Allow 38 mm (1.5 in.) below the controller for cabling clearance.
1
cFP-20xx Quick Start Guide
©
National Instruments Corporation
Vista de pagina 0
1 2 3 4 5 6 ... 18 19

Indice de contenidos

Pagina 1 - FieldPoint

FieldPointTMcFP-20xxQuick Start GuideWhat You Need to Get Set Up• cFP-20xxLabVIEW RT controller• Mounting hardware (DIN rail, panel-mount, or rack-mou

Pagina 2

IInnssttaallll SSooffttwwaarree oonn tthhee HHoosstt PPCCA. Install the software packages you plan to use, such as LabVIEW, LabVIEW RT, Lookout,M

Pagina 3 - 457 mm (18 in.)

11cFP-20xx Quick Start Guide©National Instruments CorporationC. Click the ++sign next to IIAA SSeerrvveerrwwiitthh OOPPCCin the left pane to expandt

Pagina 4

G. Enter values on the Network Settings tab of theSystem Configuration dialog box, shown in thefigure at right. If your network does not have agateway

Pagina 5 - INSTRUMENTS

I. Enter an IP address for the Time Server on theServers tab of the System Configuration dialog box,shown in the figure at right.The time server is a

Pagina 6

14cFP-20xx Quick Start Guideni.comFFiinnddiinngg aanndd CCoonnffiigguurriinngg DDeevviicceess aanndd CChhaannnneellss After you have configured

Pagina 7

C. To configure the hardware settings of a particular I/O module, right-click the device nameand select EEddiitt tthhiiss ddeevviiccee. The Device C

Pagina 8 - Primary Power Supply

16cFP-20xx Quick Start Guideni.comD. Click CChhaannnneell CCoonnffiigguurraattiioonnto access the Channel Configuration dialog box, shown in thefigur

Pagina 9

17cFP-20xx Quick Start Guide©National Instruments Corporation

Pagina 10

18cFP-20xx Quick Start Guideni.comSSaavviinngg HHaarrddwwaarree CCoonnffiigguurraattiioonn aass PPoowweerr--UUpp SSttaatteeWhen you are satisfied

Pagina 11

ni.comGo to ni.com/support for the most current manuals, examples, and troubleshooting information. Fortelephone support in the United States, create

Pagina 12

2cFP-20xx Quick Start Guideni.comMounting the Backplane on a DIN RailA. Fasten the DIN rail clip(s) to the cFP-BP-xusing a number 2 Phillips screwdri

Pagina 13

Mounting the Backplane on a PanelA. Fasten the panel-mount plates to the back of thecFP-BP-xusing a number 2 Phillips screwdriver andthe 8-32 × 5/16 i

Pagina 14

Mounting the Backplane in a Standard 19-in. RackA. Fasten the rack-mount bracket to the back of the cFP-BP-xusing the captive screws on thebracket.B.

Pagina 15

IInnssttaallll tthhee ccFFPP--2200xxxxCCoonnttrroolllleerr oonn tthhee BBaacckkppllaanneeA. Make sure that no power is connected to the controlle

Pagina 16

6cFP-20xx Quick Start Guideni.comIInnssttaallll II//OO MMoodduulleess oonn tthhee BBaacckkppllaanneeA. Align the captive screws on the I/O module

Pagina 17

IInnssttaallll CCoonnnneeccttoorr BBlloocckkss oonn tthhee BBaacckkppllaanneeIn order to connect I/O modules to input signals or to external load

Pagina 18

CCoonnnneecctt tthhee ccFFPP--2200xxxxttoo YYoouurr NNeettwwoorrkkConnect the cFP-20xxcontroller to an Ethernet network using the RJ-45 Ethernet p

Pagina 19 - *323334A-01*

C. Use a separate power supply for each module that needs external power.D. Refer to the operating instructions for the power requirements of each I/O